General Information
Application code
EII
Type version
mk2
Lamp type
TL5
Number of lamps
2 piece/unit
Number of products on MCB (16 A type B) (nom.)
12
Automatic restart
Yes
Operating and Electrical
Input voltage
220 to 240 V
Input frequency
50-60 Hz
Operating frequency (max.)
89 kHz
Operating frequency (min.)
45 kHz
Ignition method
Programmed Start
Crest factor (max.)
1.7
Power factor 100% load (nom.)
0.98
Ignition time (max.)
0.2 s
Mains voltage performance (AC)
-8%-+6%
Mains voltage safety (AC)
-10%-+10%
Earth leakage current (max.)
0.5 mA
Inrush current width
0.40 ms
Power losses (nom.)
7.9 W
Inrush current peak (max.)
45 A
Wiring
Connector type input terminals
WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
Connector type output terminals
WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
Connector type control input terminals
WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
Wire strip length
8.0-9.0 mm
Dual fixture master/slave
-  [ not specified]
Control input terminal cross section
0.50-1.00 mm²
Input terminal cross section
0.50-1.00 mm²
Output terminal cross section
0.50-1.00 mm²
Auto Insert (ALF/ADS) Wire Cross Section
0.5 mm²
System characteristics
Rated ballast-lamp power
49 W
Temperature
T ambient (max.)
50 °C
T ambient (min.)
10 °C
T storage (max.)
80 °C
T storage (min.)
-25 °C
Stable lamp operation temperature
Not Specified
T-Ignition (max.)
50 °C
T-Ignition (min.)
0 °C
Controls and Dimming
Control interface
1-10V
Regulating level power
1%-100%
Control input protection
Yes (Basic insulation)
Mechanical and Housing
Housing
L 360x30x21
Emergency Operation
Battery voltage lamp ignition
196 V
Battery voltage lamp operation
154-276
Approval and Application
Energy efficiency index
A1
EMI 9 kHz... 30 MHz
EN55015
EMI 30 MHz... 1,000 MHz
EN55022 level B
Safety standard
IEC 61347-2-3
Performance standard
IEC 60929
Quality standard
ISO 9000:2000
Environmental standard
ISO 14001
Harmonic current emission standard
IEC 61000-3-2
EMC immunity standard
IEC 61547
Vibration standard
IEC68-2-6 F c
Bumps standard
IEC 68-2-29 Eb
Humidity standard
EN 61347-2-3 clause 11
Approval marks
CE marking
ENEC certificate
VDE-EMV certificate
Temperature marking
Yes
Emergency standard
IEC 60598-2-22
Humming and noise level
Inaudible
Product Data
Full product code
871150091003530
Order product name
HF-R 249 TL5 EII 220-240V 50/60Hz
EAN/UPC – product
8711500910035
Order code
913700608766
Numerator – quantity per pack
1
Numerator – packs per outer box
12
Material no. (12NC)
913700608766
Net weight (piece)
0.310 kg
Installation Diagrams
HF-R 2 lamps TL5/PL-L/TL-D
HF-R 2 lamps TL5/PL-L/TL-D
Performance Diagrams

Recently Viewed

    • Manage your projects with MyProjects
      Use MyProjects to create, save manage and share items and projects with you colleagues and team members.
You are now visiting our Global professional lighting website, visit your local website by going to the USA website